Enclosure Ventilation Calculator

Design the exhaust for a new enclosure, or audit an existing one from measured openings and airflow. Both modes check EPA Method 204 permanent total enclosure criteria.

Mode

A name for this enclosure, such as a booth or line number.

Inside dimension.

ft

Inside dimension.

ft

Inside dimension.

ft

Percent of surface area that is open. Try smaller values to see the airflow drop.

%

Design air velocity inward through the NDOs.

fpm

Used to size or check the exhaust duct.

fpm

Makeup air delivered into the enclosure.

CFM

Required exhaust

CFM Q Out

Surface area ft²
Volume ft³
NDO area ft²
Effective NDO %
Air changes per hour ACH
Duct size calculated in
Stock duct size in
Velocity in stock duct fpm
NDO ≤ % of surface area
Face velocity ≥ fpm

Airflow by NDO size

Same enclosure, face velocity and supply air. Smaller openings need less exhaust and a smaller duct.

NDONDO areaQ OutStock ductACH

CriteriaThe 5% NDO and 200 fpm face velocity criteria come from EPA Method 204 (40 CFR Part 51, Appendix M).

Transport velocity2,000 fpm is for vapors and gases; particulate typically needs 3,500–4,500 fpm (ACGIH Industrial Ventilation manual).

Screening onlyThis is a screening calculator; final design should be reviewed by a qualified person.