Enclosure Ventilation Calculator
Design the exhaust for a new enclosure, or audit an existing one from measured openings and airflow. Both modes check EPA Method 204 permanent total enclosure criteria.
Required exhaust
CFM Q Out
Airflow by NDO size
Same enclosure, face velocity and supply air. Smaller openings need less exhaust and a smaller duct.
| NDO | NDO area | Q Out | Stock duct | ACH |
|---|
Actual face velocity
fpm through NDOs
CriteriaThe 5% NDO and 200 fpm face velocity criteria come from EPA Method 204 (40 CFR Part 51, Appendix M).
Pressure differenceMethod 204 treats a pressure drop of 0.007 in. w.c. across the enclosure as equivalent to 200 fpm face velocity, so either check can show adequate inward flow.
Transport velocity2,000 fpm is for vapors and gases; particulate typically needs 3,500–4,500 fpm (ACGIH Industrial Ventilation manual).
Screening onlyThis is a screening calculator; final design should be reviewed by a qualified person.